The Fire-Lite MMF-302-6 is an addressable six-zone interface module. Specifically, it brings conventional two-wire detection zones onto a Fire-Lite addressable panel. As a result, one module reports up to six zones using a single address.
You can wire it as six Class B (Style B) zones or three Class A (Style D) zones. The module ships in the Class B position. Then, removing a shunt sets Class A operation.
How the Fire-Lite MMF-302-6 Reports
Each monitored zone connects to compatible two-wire smoke detectors or contact devices. In addition, an external power supply feeds the detector zones. Therefore, the module supervises both the zones and that supply. Also, onboard LEDs show which zone is active.
Fire-Lite MMF-302-6 Specifications
- Six Class B (Style B) zones or three Class A (Style D) zones, one address
- External supply: 18 to 28 VDC, power-limited (0.1 Vrms ripple max)
- External supply current: 90 mA max per address in alarm; 540 mA max all six (Class B)
- Module alarm current: 40 mA (all six LEDs on)
- Maximum IDC wiring resistance: 25 ohms
- Wire gauge: 12 AWG to 18 AWG
- Temperature: 32°F to 120°F (0°C to 49°C); humidity 10% to 85% non-condensing
- Dimensions: 6.8″H x 5.8″W
Order the Fire-Lite MMF-302-6
Life Safety Consultants stocks the Fire-Lite MMF-302-6 and compatible Fire-Lite addressable panels. To order or confirm compatibility, call 1-888-557-0558. Alternatively, email sales@lifesafetycom.com.
For more information, contact the Life Safety Consultants team at (888) 557-0558, or email us at: sales@lifesafetycom.com
Additional information
| Weight | 0.8 lbs |
|---|---|
| Dimensions | 12 × 9 × 2.5 in |
| Condition | New |
| Manufacturers | Fire-Lite |
| Part Type | Module |