The SigCom MNS-100EXP is a complete mass notification system housed in one wall-mounted panel. It broadcasts emergency voice messages and tones for fire, weather, and other critical events. Unlike an add-on module, this panel operates as a standalone emergency communications system. In fact, it connects to virtually any host fire alarm panel through a single NAC circuit.
A built-in digital message unit stores up to nine messages, with 6-1/2 minutes of total capacity. Also, messages can be recorded locally in the field. A 100 Watt Class D amplifier drives four supervised speaker circuits. Each circuit can be wired Class A or Class B. Furthermore, an optional MNS-8-ZONE card expands the panel to twelve speaker circuits.
SigCom MNS-100EXP Key Features
- Reverse-polarity supervised FACP NAC primary input (9–30 VDC, 10 mA)
- Supervised dry-contact primary activation input, plus 8 prioritized contact-closure inputs
- On-board digital messaging: up to 9 messages, 6-1/2 minutes capacity, local recording
- 100 Watt high-efficiency Class D digital audio amplifier
- 4 selectable supervised speaker circuits (Class A or B), 25 Vrms standard
- Optional 70 Vrms output via the MNS-70V-XFMR transformer
- Remote microphone input, plus auxiliary audio inputs for paging and background music
- RS-232 or RS-485 communication with external systems, such as a DTX radio master box
- Field-programmable 10-minute message timeout
Expansion Options
The MNS-100EXP accepts a range of option cards. For example, the MNS-8-INPUT card adds eight supervised contact-closure inputs. The MNS-3-REL card adds common alarm and trouble relays. In addition, the MNS-NAC-REL card provides two NAC outputs and six Form-C relays. Up to 15 MNS-LOC-R local operating consoles connect through an MNS-LOC-M master card. Finally, MNS-100APB audio power boosters add output power in 100 Watt steps.
Specifications
- Primary power: 120 VAC, 60 Hz; 5 A nominal
- Internal battery backup: 10 A-Hr; 24-hour standby, 15-minute alarm
- Audio output: 100 W at 25 Vrms; one circuit to 60 W, three to 25 W each
- Enclosure: 31-5/8″H x 14-3/16″W x 4″D painted steel; surface or semi-flush mount
- Temperature range: 32°F to 120°F (0°C to 49°C); humidity 90% max, non-condensing
- Listings: ETL Listed to UL 864 (9th Ed.) and UL 1711 (4th Ed.); complies with UL 2572
- Meets NFPA 72 and UFC 4-021-01 requirements
For more information, contact the Life Safety Consultants team at (888) 557-0558, or email us at: sales@lifesafetycom.com
Browse Related Products
Additional information
| Weight | 10 lbs |
|---|---|
| Dimensions | 19 × 14 × 4 in |
| Condition | New |
| Manufacturers | SigCom |
| Part Type | Speaker |
| Compatible Panels | SigCom MNS-100 system |
| Compatible Bases | MNS-100BAS |
| Cross Reference | MNS-100BAS, MNS-100APB |
| Specification | Zone/channel expansion module for MNS-100 system |